HygroFlex5-EX (two-wire current loop, loop-powered): 10 ... 28 VDC depending on the loads connected to the
outputs. The minimum supply voltage can be calculated as follows:
V min = 10 V + (0.02 A x load*) *Load resistance in ohms.
The minimum supply voltage for the maximum load of 500 Ω is 10 V + (0.02 A x 500 Ω) = 20 VDC. If both output
circuits are closed, the maximum current consumption is 40 mA.
The device must be properly closed when in operation in order to achieve explosion protection.
The HygroFlex5-EX reads out the data of the connected probe.
The user can configure the HygroFlex5-EX with the ROTRONIC HygroSoft software to calculate one of the following
parameters:
•Dew point (Dp) above and below freezing point
•Frost point (Fp) below freezing point and dew point above freezing point
•Wet-bulb temperature (Tw)
•Enthalpy (H)
•Vapor concentration (Dv)
•Specific humidity (Q)
•Mixing ratio by weight (R)
•Vapor concentration at saturation (Dvs)
•Vapor partial pressure (E)
•Vapor saturation pressure (Ew)
Note:
Some of the above-mentioned parameters depend on the value of the atmospheric air pressure.
The user can define a fixed atmospheric air pressure value with the ROTRONIC HygroSoft software.
Using the ROTRONIC HygroSoft software, each of the two analog output signals can be assigned to one of the
following parameters:
•Measured relative humidity (%RH)
•Measured temperature (°C/°F)
•Calculated parameter
The scale of each analog output can be set within the numerical limits of -999.99 and 9999.99.
The analog output signals are generated by 16-bit D/A converters.
The service connector (UART interface with mini-USB port) allows connection of the HygroFlex5-EX
to a PC running the ROTRONIC HygroSoft software. A service cable is needed for this. See chapter Maintenance
for the location of the service connector and the type of service cable.
• The service connector is used for configuration and for updating the firmware of the HygroFlex5-EX.
The HygroFlex5-EX may only be operated with the following ATEX probe models:
HC2-SM-EX (standard probe)
|
HC2-IM102-EX (cable probe 2 m, probe length 125 mm)
HC2-IM105-EX (cable probe 5 m, probe length 125 mm)
HC2-IM110-EX (cable probe 10 m, probe length 125 mm)
HC2-IM302-EX (cable probe 2 m, probe length 285 mm)
HC2-IM305-EX (cable probe 5 m, probe length 285 mm)
HC2-IM310-EX (cable probe 10 m, probe length 285 mm)
|
HC2-IE102-EX (screw-in probe with 1/2'' G thread, cable length 2 m)
HC2-IE105-EX (screw-in probe with 1/2'' G thread, cable length 5 m)
HC2-IE110-EX (screw-in probe with 1/2'' G thread, cable length 10 m)
HC2-IE302-EX (screw-in probe with 1/2'' NPT thread, cable length 2 m)
HC2-IE305-EX (screw-in probe with 1/2'' NPT thread, cable length 5 m)
HC2-IE310-EX (screw-in probe with 1/2'' NPT thread, cable length 10 m)
|
Outputs
Functions |
Describtion |
► Humidity and temperature measurement |
The connected probe is read out digitally and its measured values shown and outputted at the analog outputs. |
Measurement loop validation
Functions |
Describtion |
► Operation in simulator mode |
Generation of fixed values for humidity, temperature and the calculated parameter. Can be configured, enabled or disabled. |
Safety
Functions |
Describtion |
► Write protection |
Protection against unauthorized digital access. Can be configured, enabled or disabled. |
► Menu access from keypad |
Used to prevent accidental or unauthorized changes to the system settings by disabling the MENU key. Can be enabled or disabled. |
PROCESS PROTECTION / PROTECTION OF OTHER DEVICES
Functions |
Describtion |
► Limit humidity to 100% RH |
This function prevents the humidity signal from exceeding 100% RH when condensation forms on the sensor. Can be enabled or disabled. |
► Out-of-limit value alarm |
Used to define the normal range for humidity, temperature and the calculated parameter, dependent on the application. Out-of-limit values trigger a digital alarm. Can be configured, enabled or disabled. |
► Fixed value on alarm |
Used to define a fixed output value for temperature or humidity in the event of a defective sensor or quality alarm. Can be configured, enabled or disabled. |