<< Click to Display Table of Contents >> Navigation: Hardware Overview > Sensors and Probes > CCD-S > Housing |
Functions |
Description |
Diameter |
32 mm (1.26") |
Length |
76 mm (3") |
Housing material |
Polycarbonate, black |
All CCD probes use the same connector (male).
Connection diagram (7-pin connector, male – view: probe side)
|
Connection diagram (7-pin connector, controller side) |
The CCD is supplied with a standard filter.
Mechanical installation
For best measurement results, observe the following points:
oFor indoor air quality measurements, the CCD should be installed at the light switch height (roughly 1200 mm from the floor)
oFor life safety measurements, the CCD should be installed at socket level (roughly 450 mm from the floor)
Use Rotronic extension cables. These allow a maximum length of 5 m.