<< Click to Display Table of Contents >> Navigation: Help > Practical Topics > Understanding MODBUS > Guidance for MODBUS Communication with the RMS LAN Devices |
RMS LAN devices (except the RMS-Converter) are based on Little Endian memory organisation (The device firmware provides the MODBUS information starting with the most significant byte.)
When selecting the MODBUS byte order in RMS-CONFIG, the settings are based upon the Little Endian format:
Little Endian Format |
---|
WordSwap |
ByteSwap |
ByteAndWordSwap |
NoChange |
When Big Endian format is required, please select the following MODBUS byte order in RMS-CONFIG:
Big Endian Format |
Setting in the RMS Config Menu |
---|---|
ByteSwap |
WordSwap |
WordSwap |
ByteSwap |
NoChange |
ByteAndWordSwap |
ByteAndWordSwap |
NoChange |