Operating modes and wiring

<< Click to Display Table of Contents >>

Navigation:  Humidity & Temperature Devices > Transmitter > XB32A >

Operating modes and wiring

The safety of the installed system, where the device is integrated, is the responsibility of the builder of the system.

 

 

 

General wiring guidelines

 

Power supply wiring

Heavy machinery and instrumentation should not share the same power supply wiring. If this cannot be avoided, noise filters and surge protectors should be used. Most UPS devices have those features already integrated.

 

General guidelines for signal cables

The following guidelines are derived from European Standard EN 50170 for the transmission of signals by copper wires. When planning an installation, the rules provided by EN 50170 should be followed under consideration of local circumstances to determine the position of machines and equipment.

 

All ROTRONIC products are tested for Electromagnetic Compatibility according to EMC Directive 2014/30/EU and following European standards:

 

- EN 61000-6-1 ; EN 61000-6-2 ;

- EN 61000-6-3 ; EN 61000-6-4 ; + A11

 

Whenever the level of electromagnetic interference is expected to be high, both the instruments and signal cables should be placed as far away as possible from the source of interference.

 

In general, signal cables should be installed in bundles or channels / conduits, separate from other cables as indicated in the table below:

 

Bus signals such as RS485

Data signals for PCs, printers etc.

shielded analog inputs

unshielded direct current (<= 60V)

shielded process signals (<= 25 V)

unshielded alternate current (<= 25V)

coaxial cables for CRT monitors

in common bundles or channels / conduits

direct current from 60 V to 400 V (unshielded)

alternate current from 25V to 400 V (unshielded)

in separated bundles or channels /

conduits, without minimum distance /

direct and alternate current > 400 V (unshielded)

Telephone lines

lines leading into EX-rated areas

in separated bundles or channels /

conduits, without minimum distance

 

Lightning protection

Cabling in areas with a risk of lightning requires a lightning protection. For cabling underground in between buildings, we recommend the use of special fiber optic cables. If this is not possible, use copper cables that are suitable for underground installation.

 

 

 

Cable grip and cable specifications

The XB32A is supplied either with M16 sealing cable. The M16 cable grip provides effective sealing only with cables having the proper outside diameter. Preferably, use a cable with an outside diameter of 6 to 7 mm (0.236 to 0.275 inch) with 18 AWG wires.

 

 

Wiring and terminal block diagrams

 

XB3: 3-wire transmitter

 

XB-3wire-electrical-diagram-voltage-outputs

 

The maximum permissible cable length can be determined under consideration of the voltage drop caused by the current flowing to the devices connected to the unit. The voltage drop in the cable depends both on cable resistance and on the equivalent resistance of the devices connected in parallel to the unit. The total resistance connected to each unit output should be at least 1000 ohms. Cable resistance should not be more than 1/1000 of the load resistance.

 

Minimum load requirements apply to the external device or circuit connected to the XB3 transmitter. These requirements are defined in the “Operation” chapter

 

XB-3wire-electrical-diagram-current-outputs

 

The maximum permissible cable length, connecting the unit to other devices, is determined by the total resistance resulting from the addition of the cable resistance and that of the devices connected in series with the unit. This resistance should not exceed 500 ohms.

 

XB-3wire-transmitter-terminal-block-diagram

 

Measuring humidity or temperature only

Operation of the XB3 does not require both current loops to be closed. When using the XB3 to measure either

humidity only or temperature only, close only the loop that is being used.

 

 

 

Optional terminal block - Pt100 direct XB3

 

Terminal block K3 is present only when the XB transmitter is equipped with an additional Pt100 RTD installed on the probe. This version is not sold anymore, but for customers reference:

 

XB-3wire-transmitter-terminal-block-diagram_PT100-direct-XB3

 

Grounding (all models)

We generally recommend grounding the (-) side of the power supply, especially if the electronics will be subjected to a low humidity environment (35 %RH or less).