Default Configuration

<< Click to Display Table of Contents >>

Navigation:  Humidity & Temperature Devices > Transmitter > XB32A > Customer adjustment >

Default Configuration

Configuration of the XB transmitter by the user and access to its functions requires a PC with the ROTRONIC HW5 or HygroSoft installed. Service cable AC3006 or AC3009 is used to connect the XB service connector to a USB port of the PC (see Maintenance -> Service Cable).

 

 

Configurable Settings

Factory default

Unit system (Metric or English)

As per ordering code

Analog signal type (4…20 mA)

As per ordering code

Psychrometric calculation

As per ordering code

Output 1 parameter, scale and unit

As per ordering code (%RH or DP)

Output 2 parameter, scale and unit

Temperature, unit as per ordering code

 

 

 

Functions

Factory default

Humidity / temperature adjustment

Enabled

Device write protection

Disabled

Limit humidity output to 100 %RH

Enabled

Out-of-limit value digital / display alarm

Disabled

Simulator mode

Disabled

 

 

For a detailed description of all functions see AirChip3000

The factory default setting for dew / frost point calculation is frost point below freezing