<< Click to Display Table of Contents >> Navigation: Help > Troubleshooting > Previous Manuals > E-SM-RMS-WEB > System Startup > Devices and Measuring Points > Measuring Point Settings |
The RMS device has the following properties and setting possibilities:
Property |
Description |
---|---|
Info |
|
ID |
Unique ID for the measuring point (MPT-xx) |
Type |
Measuring point type or parameter oMeasuring element Measuring element (e.g. HygroClipD) that is connected directly to the device. oPsychrometric Calculation Psychrometric calculation from humidity and temperature. oArithmetic Calculation Arithmetic calculation (e.g. difference, sum, average, PT1 filter, etc.) oVirtual button Logical switch that can be operated by the user directly. oSystem measuring point A system measuring point counts events and can be monitored with an alarm threshold like a normal measuring point. It can also be used to measure the signal strength. Types of system measuring points: ▪Switch input counter Number of state changes of a logical input1 ▪Alarm time counter Duration of the alarm state2 of a measuring point. ▪Measuring point alarm counter Number of measured values of a measuring point in alarm state3 ▪Device refresh counter Counts when a device sends new measured values ▪Signal strength Measures the signal strength and writes it in the database like a measured value ▪Pending reminders ▪Pending warnings ▪Pending alarms ▪Pending errors ▪CPU load CPU load in % ▪Memory load Memory load in % ▪Measuring point updates Number of updated measuring points (valid for all measuring points, also calculations and counters) ▪Pending commands Number of Pending commands ▪Software exceptions Number of software errors ▪Active users Number of active users based on RMS pages loaded ▪Page loads Number of loaded RMS pages |
Status |
oEnabled Measuring point is enabled in the system. oDisabled The system does not receive any data from the measuring point and alarms are also not triggered. |
Serial number |
Serial number of the probe (only in the case of interchangeable RMS probes) |
Device |
Name and ID of the device, including direct link to device settings |
Last refresh |
Time that has passed since the system last received data from the measuring point |
Settings |
|
Name |
Freely selectable measuring point name |
Regulation status |
Freely selectable regulation status (GMP / GLP / etc.) |
Comment |
Freely selectable comment |
Details |
Settings for a calculated measuring point or system counter |
Group(s) |
Group allocation (more than one group can be specified) |
Alarm |
|
Mode |
oOff No alarm evaluation. oMeasuring point The alarm limits are defined directly for the measuring point. oAlarm triggers The alarm limits are defined as alarm scheme (alarm triggers). |
Warning |
|
Enabled / Disabled |
Only enabled alarms are processed in the system |
Lower limit |
Lower limit value |
Upper limit |
Upper limit value |
Hysteresis |
Hysteresis |
Delay |
Delay in alarm notification |
Alarm |
|
Enabled / Disabled |
Only enabled alarms are processed in the system |
Lower limit |
Lower limit value |
Upper limit |
Upper limit value |
Hysteresis |
Hysteresis |
Delay |
Delay in alarm notification |
1 Logical inputs can only have the states "1" or "0".
2 Alarm states are: "Warning" or "Alarm"
3 Alarm states are: "Warning" or "Alarm"
The following functions are available for editing measuring points:
Function |
Description |
---|---|
New |
Add new measuring point |
Archive |
All information of the measuring point data set is archived and can be viewed in the archive. The data archive is described in the E-OM-RMS-WEB document. oGeneral measuring point information oMeasured values oEvents oCalibration data oDocuments |
Delete |
Delete measuring point irretrievably.4 5 To delete a device, it is also necessary to enter a text in order to prevent accidental deletion of a device. |
Save |
Save measuring point settings |
4 So that measuring points can be deleted, this function must be enabled in the system settings.
5 Alarms relating to this measuring point are ended automatically and labels deleted from the "Layout" view.