       << Click to Display Table of Contents >> Navigation: Hardware Overview > Sensors and Probes > HCD-Sx > Device description | 
    
Functions  | 
Description  | 
Measured parameters  | 
Relative humidity and temperature using the ROTRONIC HYGROMER® HT-1 and a Pt1000 temperature sensor  | 
Humidity measurement range  | 
0…100 %rh  | 
Temperature measurement range  | 
-40…+85 °C (-40…+185 °F)  | 
Accuracy  | 
±0.8 %rh, ±0.1 K at 10…30 °C  | 
Diameter  | 
15 mm (0.6")  | 
Length  | 
108 mm (3.3")  | 
Housing material  | 
Polycarbonate, black  | 
Standard filter  | 
Polyethylene, 40 µm  | 
Weight  | 
10 g (0.35 oz)  | 
Power Supply  | 
The HCD requires a power supply of   | 
Digital interface  | 
The HCD probe has a UART interface with an logical level of 2.5 V  | 
Modbus  | 
Measurement values and serial number can be read out if the probe is to be used out of the RMS - please see Modbus  | 
Adjustment  | 
•1-point or multi-point humidity adjustment/calibration •1-point or 2-point temperature adjustment/calibration •Output the last adjustment/calibration, with date •Produce an adjustment/calibration log  | 
Sensor alarm  | 
The probe outputs a digital alarm if the sensor has a short circuit or open circuit. This function cannot be deactivated.  | 
Cable length  | 
maximum 3 m  | 
Configurable settings  | 
Factory default  | 
Unit of measurement (metric/English)  | 
Metric  | 
Psychrometric calculation  | 
None  | 
Communication protocol  | 
MODBUS  | 
MODBUS address  | 
0  | 
Device name  | 
HCD  | 
Functions  | 
Factory default  | 
Humidity/temperature adjustment  | 
Factory adjusted  | 
Write-protection for device settings  | 
Disabled  | 
Simulator mode  | 
Disabled  |