<< Click to Display Table of Contents >> Navigation: Humidity & Temperature Devices > Transmitter > HFM53 > Technical specification |
General |
Description |
Device type |
Humidity temperature transmitter with analog output signals |
Range of application |
-40...60 °C, 0…100 %RH, non condensing |
Mounting type |
Wall mount |
Circuit type |
3-wire |
Calculated parameters |
Dew point (Dp) above and below freezing Frost point (Fp) below freezing and dew point above freezing Wet bulb temperature (Tw) Enthalpy (H) Vapor concentration (Dv) Specific humidity (Q) Mixing ratio by weight (R) Vapor concentration at saturation (Dvs) Vapor partial pressure (E) Vapor saturation pressure (Ew) |
Power supply and connections |
Description |
Supply voltage |
15…40 VDC or 12…28 VAC |
Current consumption |
< 50 mA |
Polarity protection |
Protective diode on V+ |
Analog Output |
Description |
Quantity |
2 |
Assignment |
Outputs can be freely assigned to each measured value. |
Default setting assignment |
Output 1 = Humidity or dew/frost point Output 2 = Temperature |
0...20 / 4...20 mA 0...1 /0...5 / 0...10 V |
|
Default setting Ranges |
4...20 mA |
Measuring signal |
Freely scalable |
Accuracy @ 23 °C |
Current output: ± 20 µA Voltage output: ± 1 mV |
Measurement Interval |
1 s |
Short-circuit protection |
Yes |
Load resistance |
max. current output: 0 to 500 Ω min. voltage output: 1 kΩ |
Housing Specifications |
Description |
Dimensions |
125 (W) x 100 (H) x 60 (D) mm |
Weight |
692 g |
Housing material |
Aluminum die cast |
IP protection |
IP651 |
Cable Connections |
1x M12, screw terminals |
Conformity with standards |
Description |
EMC directives |
EMC Directive 2004/108/EG: EN 61000-6-1: 2001, EN 61000-6-2: 2005 EN 61000-6-3: 2005, EN 61000-6-4: 2001 + A11 |
Soldering material |
Lead free (RoHS-Directive 2011/65/EU) |
FDA/GAMP directives |
GAMP5 |
1IP65 is only fulfilled, when the necessary number of conductors is used so that the M12 cable strain provides an effective seal