<< Click to Display Table of Contents >> Navigation: Humidity & Temperature Devices > Probes > XD > Housing |
Functions |
Description |
Diameter |
15 mm (0.6") |
Length |
140.3 mm (55.2") |
Housing material |
Polycarbonate, black |
For best measurement results, please consider the following points:
oInstall the probe at a representative location for the process to be measured.
oAvoid the following:
▪Probe near a heating or cooling element, a cold/hot wall, in direct sunlight, etc.
▪Probe near a steam inlet, humidifier, or atmospheric precipitation
▪Pressure fluctuations (e.g. in compressed air systems)
oThe probe should not be installed above a heating element.
oThe airflow might be faster than 1 m/s if possible
If installed through a wall, make sure the probe is inserted as far as possible into the environment being measured.
During installation, make sure that no condensation can collect on or in the probe and cause a short circuit at the sensor connections. Probes should be installed with the sensors at the bottom. This allows waste heat from the electronics to escape upward. If not possible, then horizontal installation is also acceptable.