HL-NT communication by the converter

<< Click to Display Table of Contents >>

Navigation:  Help > Troubleshooting > Using RMS >

HL-NT communication by the converter

The converter programs the HL-NT device as follows:

oProperties

LogfileMode

LOG

Delete old data

No

Relais Settings

All Off

Write-Protection

Off

Current time

UTC time

Alarm Settings

Will not be overwritten, but ignored by the converter and RMS

 

oLog Settings (Same for all Probes)

Interval

1 Min

Create new file

Every Day

Humidity

On

Temperature

On

Calculation

Off

Start time

1.1.2000

Stop time

1.1.2050

 

Files on the Flash card

oAll XLS files will be deleted

oAll LOG files older than 7 days will be deleted

 

What to do after a communication interruption:

oInterruption between Converter and HL-NT

After the interruption, the RMS requests the missing data from the converter

The converter reads the data from the flash card of the HL-NT

oInterruption between RMS and Converter

The converter has an internal database and stores the data for the last 7 days.

After the interruption, the RMS requests the missing data from the converter