Device description

<< Click to Display Table of Contents >>

Navigation:  Hardware Overview > Input and Output Devices > RMS-DO-L-R >

Device description

General information

Functions

Description

Dimensions

108 x 89.7 x 62.2 mm

Housing material

PC (Polycarbonate)

Weight

155 g

Power Supply

The module has the following two power supply variants:

o24 VDC ±10 % / <100 mA1 via terminals (V+ / V-)

oPower over Ethernet (PoE), per standard IEEE 802.3af, Class 1

Interface

The device is operated completely via the LAN interface.

Cable length

<3 m min. Cat. 5

1 Power supply requirements: 24 VDC ±10 % / >4 W nominal / <15 W limited power source

 

 

RMS Digital Output Module

The digital output module provides two digital outputs as well as an Ethernet connection for integration into the Rotronic Monitoring System (RMS).

 

The device provides the following basic functions:

Two digital output channels

Relays can be read or set via interface

Firmware update

 

 

Inputs / Outputs

The RMS devices have different inputs or outputs. Devices with replaceable probes (E2 connector) automatically detect the measuring parameters of the probe.

The following table lists the main types of RMS devices:

Data Loggers for Interchangeable Probes

RMS-LOG-L

Data logger, external probe, LAN

RMS-LOG-868

Data logger, external probe, 868 MHz

Temperature Data Loggers

RMS-MLOG-T10-xxx

Data logger, external probe, 1 x NTC, 868 / 915 MHz

RMS-LOG-T-xxx

Data logger, internal probe, 1 x NTC, 868 / 915 MHz

Analog Input Modules

RMS-MADC-xxx-A

Data logger, 1 x analog input, 868 / 915 MHz , 0(4)…20 mA

RMS-MADC-xxx-V

Data logger, 1 x analog input, 868 / 915 MHz , 0…10 V

RMS-8ADC-L-R-A

8 x analog input, LAN, mounting on DIN top hat rail, 0(4)…20 mA

Digital Input Modules

RMS-DI-L-R

Data logger, 2 x digital input, LAN, mounting on DIN top hat rail

Digital Output Modules

RMS-DO-L-R

2 x digital output, LAN, mounting on DIN top hat rail

 

 

RTCC (Real Time Clock Calendar)

The device has a real time clock calendar. The time is synchronized continuously when connected to the server.

 

 

Data Output

The outputs are active as soon as the software configuration has been completed.

Following values are saved:

time stamp

actual status of the digital outputs

 

 

Operating and display elements

The device has a button and a multicolored LED for operation and display of the operating state. The button is used during commissioning or for switching the device off in battery operation. The device flashes only if the operating state changes, or if the push-button is pressed briefly. The displayed device state is updated for each event. In order to prolong the operating time in the battery operation, the LED flashing can be deactivated.

 

oSignal lamp and push-button

Pairing

Trigger

Action

LED

1 s press

Confirms pairing

n x orange, the indicator flashes while the paring request is running

Device status update

Trigger

Action

LED

1 s press

Shows the current status

1 x green, measurement & data transmission successful

1 x orange, measurement successful, data transfer failed

Automatic

At status change at the relay