Add an RMS-LOG-T30-868/915 to RMS

<< Click to Display Table of Contents >>

Navigation:  Hardware Overview > LOG Dataloggers > RMS-LOG-T30-868/915 > Step-by-Step >

Add an RMS-LOG-T30-868/915 to RMS

Pairing / Integration into RMS

Step 1

Open a web browser on your computer, log in to the RMS software and select "Tools" > "Setup" > "Device" > "New" > "Wireless device"

 

Wireless_add_new_device

 

Step 2

Select the gateway you want your wireless data logger to be connected to.

 
NOTE:

The gateway must first be integrated.

 

Pairing_Wireless_RFLogger_Select_GW

 

Step 3

Press the device's button

 
IMPORTANT:
Please press the button after the LED starts flashing orange.

 

Pairing_Wireless_RFLogger_New_device

 

Step 4

The LED flashes green when connection is successful.

 

oConfigure the device and measurement point.

Pairing_Wireless_RFLogger_device_configuration

oFinish the configuration.

 

 

Unpairing

There are two ways to unpair wireless devices:

1.Delete devices from RMS

Step 1

"Tools" > "Setup" > "Devices" > select the device to unpair > click "Delete" (right side of the screen)

 

Wireless_unpairing

 

Step 2

A Warning appears: Type the reason for deleting the device for the audit trail of the RMS.

 

Wireless_unpairing_reason_to_delete

 

Step 3

After clicking "OK", it is necessary to wait one further interval time to unpair the device correctly.

Step 4

The device signalizes the unpairing process by the LED flashing red three times.

 

Important:

Make sure that the device is powered during this last interval (i.e. do not remove the battery). If the power is interrupted, the device does not recognize that it is unpaired. In this situation, it cannot be paired again easily.

 

2.Press the button

As an alternative to the process above, it is possible to unpair the wireless device permanently by pressing the button for approximately 5 seconds.

Important:

Beware that the device is unpaired, but the devices still remains within the RMS. The RMS does not notice this device unpairing.

oThe RMS will still display the device with a timeout  

oThe RF address of this device is still occupied for the system

This method is useful if the customer wants to rebuilt or restructure the system.